From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

Explore Jubang Group’s development history, intelligent manufacturing base, R&D platforms, CNAS-accredited laboratory and global project service capabilities.

A dry-type transformer partial discharge test report is insulation-test evidence, not a stand-alone promise about service life or fitness for energization. It should connect the reported apparent-charge result to the identified transformer, the test circuit, applied-voltage sequence, calibration record, background-noise conditions and the agreed acceptance basis.

Partial discharge is a localized electrical discharge that only partly bridges insulation. In a dry-type transformer test, the report records electrical evidence obtained under a defined test arrangement; it does not directly measure the physical charge at a possible discharge site.
IEEE C57.124 addresses detecting partial discharge in dry-type transformers and measuring associated apparent charge at the terminals during applied AC-voltage testing. IEC 60270 provides the wider charge-based measurement framework, including measurement circuits, calibration and discrimination from external interference.
The practical review question is not “Does this report contain a low number?” It is “Can a qualified reviewer trace the number to the tested transformer and the controlled conditions that produced it?” If that connection is absent, the record cannot support a reliable comparison with the agreed test plan.
IEC 60270 defines apparent charge as the quantity that would produce the same instrument reading if injected at the terminals of the test object in the specified test circuit. It is normally expressed in pC, but it is not the local charge involved at a discharge site.
That definition matters when comparing reports. Change the object connection, coupling arrangement, measuring impedance, frequency band, calibration position or interference environment, and a pC figure may no longer mean the same thing for a review purpose.
| Report item | What it tells the reviewer | What it cannot establish alone |
|---|---|---|
| Apparent-charge reading | The stated measurement-system response at the documented condition | Defect size, exact location or lifetime |
| Test voltage and sequence | The electrical condition at which the reading was recorded | A generic acceptance limit for every design |
| Measuring bandwidth and circuit | How the electrical measurement was arranged | That another laboratory will obtain an identical trace |
| Acceptance basis | Which controlled requirement was used for the decision | Compliance with requirements not named in the plan |
Avoid asking a supplier to apply one value to every dry-type transformer. The applicable standard edition, transformer design, contractual specification, applied-voltage sequence and acceptance authority must be named before a criterion can be evaluated.

Before reading a trace, verify that the report identifies the transformer well enough to prevent a document mix-up. The report number, test date, manufacturer identity, transformer serial number and nameplate details should point to the same object named in the purchase and test documentation.
Electrical identity is equally important. Record the winding arrangement, rated voltages, terminal designations, tap position where relevant, grounded or ungrounded terminals, accessories connected during the test and any declared configuration that can affect the electrical arrangement.
| Field group | Include in the report | Review action |
|---|---|---|
| Transformer identity | Manufacturer, type, serial number, ratings and winding information | Match to the purchase data and nameplate record |
| Tested configuration | Terminals energized, terminals grounded, tap position and connected accessories | Match to the approved test plan |
| Test facility | Laboratory identity, date and responsible test personnel | Retain with witness and deviation records |
| Measuring system | Detector, coupling device, measuring impedance, calibrator and instrument identifiers | Confirm the stated equipment matches the calibration record |
| Result record | Voltage points, apparent-charge readings, traces and observations | Check that every result has a condition and evaluation basis |
Nameplate work is a useful precursor to this check. The distribution transformer nameplate guide explains why ratings and connection data should be controlled before technical records are compared.
Calibration ties the instrument scale to a known injected charge in the stated arrangement. The record should identify the calibrator, its status, the injected value or values, the injection location and the response obtained before the measurement run. A calibration statement without the test-circuit context is incomplete evidence.
Background noise and interference need their own record. IEC 60270 distinguishes signals caused by the test object from extraneous signals, so the report should show how the baseline was observed, what noise level or pattern was present, and what action was taken when interference affected interpretation.
Where the test uses a temporary connection, confirm cable routing, shielding and grounding arrangements in the test record. These details can affect the interference environment and should be reviewed by the responsible test authority rather than inferred from a final result table.
The voltage history belongs beside the result. A report should state the test voltage levels, sequence, duration or dwell where specified, phase or terminal under test, and the point at which each trace or apparent-charge value was captured. A result table without this sequence is difficult to compare with a controlled plan.
Phase-resolved patterns, time-domain records or other traces can help show the observed signal behavior. They remain supporting evidence: their interpretation depends on the instrument settings, noise environment, calibration and qualified engineering review.
| Controlled input | What the report should show | Why it matters |
|---|---|---|
| Applicable document set | Standard edition, purchaser specification and agreed test procedure | Prevents a generic criterion from replacing the agreed one |
| Voltage sequence | Applied levels, order, duration where required and result point | Links each result to its electrical condition |
| Trace record | Trace type, associated terminal or phase and time or voltage reference | Preserves the observation for review |
| Evaluation statement | Stated criterion and named decision authority | Separates laboratory measurement from project acceptance |
| Deviation record | Any change to the agreed setup, sequence or data quality | Makes escalation possible before release |
IEC 60270 is a horizontal measurement standard; IEC 60076-11 and the purchaser’s controlled specification provide the transformer-specific context. Use those documents as inputs to a test plan, not as a reason to copy a universal pC limit into an RFQ.
Factory PD measurement is commonly planned around a known transformer, controlled connections, defined equipment and an agreed production or witness procedure. Its value is the documented evidence for that defined test event.
Field diagnostic work may have a different purpose. Site connections, nearby electrical activity, installation condition, access constraints and background interference can all change the method and the confidence needed to interpret a signal. A field test authority should define the method, safety controls, comparison basis and action thresholds for the actual site.
Do not compare a factory result and a field result as if they were interchangeable simply because both use pC. First establish whether the object configuration, circuit, calibration, voltage condition and interference treatment are sufficiently comparable for the stated engineering decision.
For adjacent project inputs, the dry-type transformer ventilation guide can help document room conditions, while the transformer protection relay guide keeps test evidence separate from protection-setting responsibility.
An RFQ or witness request should ask for the report format before the test starts. This lets the purchaser, manufacturer and test authority agree which object identifiers, circuit records, calibration evidence, traces, acceptance inputs and deviations must be retained.
If a report is missing an identifier, circuit diagram, calibration record, noise explanation, trace reference or agreed evaluation basis, pause the release decision and escalate the gap to the responsible test or engineering authority. Requesting a new conclusion without resolving the missing evidence can conceal the actual decision risk.
Once the equipment scope and documentation requirements are defined, a JUBANG SCB dry-type transformer range can be discussed as product-family context. It should not be treated as evidence of partial-discharge performance, a test result, a standard claim or a substitute for the controlled test plan.

Use this guide to define what a dry-type transformer PD report should contain and to prepare a documentation request. Do not use it to set an acceptance value, diagnose a site signal, locate a discharge source, certify a transformer or authorize energization.
For a project-specific documentation discussion, contact JUBANG with the transformer data sheet, controlled test plan, required standard edition, report template and the named acceptance authority.
It is a dielectric-test measurement that detects electrical PD signals and records apparent charge at transformer terminals under a defined AC test arrangement. Its meaning depends on the identified test object, circuit, voltage sequence, calibration and evaluation basis.
Apparent charge is the charge-related quantity that gives the same measuring-instrument response when injected at the test-object terminals in the specified circuit. It is commonly reported in pC, but it is not a direct measurement of local discharge charge or defect size.
Calibration checks the response of the measuring arrangement using a known injected charge. The report should identify the calibrator, injection point, injected value and response so that the apparent-charge scale can be reviewed in context.
It should record the observed baseline or interference condition and explain how signals not attributed to the test object were handled. A result without noise context can be difficult to interpret or compare.
The applicable criterion must come from the controlled test plan, including the relevant standard edition, transformer-specific requirements and purchaser specification. This guide does not provide one universal pC limit.
No. Factory and field work can use different connections, environmental conditions, interference controls and objectives. Compare them only after a qualified authority confirms that the methods and contexts support the intended decision.
Include the transformer manufacturer, type, serial number, ratings, winding and terminal configuration, report number, date, test facility, instrument identifiers and calibrator details. These fields let the reviewer connect the result to the actual test object and setup.
Escalate when the report lacks a test-object identifier, circuit diagram, voltage sequence, calibration record, background-noise explanation, trace reference, deviation record or agreed acceptance basis. The responsible test or engineering authority should decide the next action.