From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

Explore Jubang Group’s development history, intelligent manufacturing base, R&D platforms, CNAS-accredited laboratory and global project service capabilities.

Transformer protection relays help a project detect defined electrical faults, apply agreed backup protection and bring condition-device signals into a coordinated trip, alarm and record scheme. They do not become a complete protection design until the transformer, CTs, winding connection, grounding, network study and operating philosophy have been confirmed.

A transformer relay scheme separates conditions that may require rapid isolation from conditions that require backup clearing, alarm, blocking or recorded evidence. IEEE’s transformer-protection guide describes a scope that includes fault types, relay application, CT behavior during system faults, fault clearing and post-trip re-energization.
The useful question is therefore not “Which relay is standard?” but “Which faults, operating states and interfaces must this project cover?” That framing keeps the transformer, switchgear, upstream and downstream protection, control power and operating authority in the same review.
An internal fault, an external through fault and an abnormal temperature signal do not present the same risk or need the same response. The selected scheme must show which device detects each condition, which breaker or switch receives a command, which signals remain alarms, and who can authorize restoration.
For a new installation or retrofit, start with the approved one-line diagram and protection philosophy. Then compare the actual equipment interfaces with the fault-study cases instead of transferring settings or logic from another transformer.
Differential protection compares currents associated with the transformer zone and is commonly used as a primary internal-fault function. Its application depends on the actual CT arrangement, transformer ratio, winding connections and the relay’s compensation and restraint approach.
Overcurrent elements can provide backup coverage for defined faults or support coordination with adjacent protection. Their role cannot be chosen from transformer MVA alone because fault source strength, feeder contribution, clearing paths and the chosen coordination method change the required review.
Residual, neutral overcurrent and restricted earth-fault functions may be considered where the winding connection, neutral availability, grounding method and CT arrangement support the intended coverage. A grounded-wye winding and a delta winding do not present the same earth-fault information to the protection system.
The fault study and grounding design decide what can be detected, from which side and with what selectivity. Do not treat an earth-fault function name as proof that a project has complete ground-fault coverage.
Oil-immersed transformer arrangements may include Buchholz, pressure-relief or temperature devices, while dry-type and other configurations use different condition inputs. These devices should be treated as separate functional categories because their presence, contacts and intended alarm or trip action depend on the supplied construction and accessories.
Ask for the manufacturer’s terminal and accessory documentation, then place every available contact in the project trip matrix. A relay cannot create a missing device signal, and a supplied contact should not be assumed to trip until its logic is documented and tested.

Reliable relay application begins with a controlled engineering input set. The relay model, CT schedule and transformer drawing need to describe the same electrical arrangement.
Provide rated power, rated voltages, winding count, vector group, tap arrangement, impedance data, neutral availability and the latest one-line diagram. Include the intended operating states, such as parallel operation, bus ties, generation connection or transformer outage arrangements, because each state can alter current paths and available fault contribution.
Provide CT locations, ratios, secondary ratings, accuracy information, polarity, terminal drawings and the protection cores assigned to the scheme. Also identify breaker trip circuits, lockout devices, auxiliary contacts, control-power source and any existing relay or bay-controller interfaces.
| Input group | Why it matters | Typical owner |
|---|---|---|
| Transformer nameplate and data sheet | Establishes winding, ratio and connection context | Transformer supplier and project engineer |
| CT schedule and drawings | Defines measured current paths and interfaces | Protection engineer and panel builder |
| Grounding drawing | Establishes the earth-fault return path | System design authority |
| Fault-study cases | Tests prospective duty and coordination cases | Protection-study authority |
| Protection philosophy | Assigns primary, backup, alarm and trip intent | Asset owner and protection authority |
Vector group and grounding are not nameplate details to be appended after relay selection. They affect how currents are represented across windings and which earth-fault paths may be visible to the scheme, so they belong in the initial protection review.
Fault-study information gives the protection engineer the prospective cases needed to assess selectivity and clearing boundaries. The study should identify relevant source contributions, transformer operating states, network configuration, protection devices and assumed breaker clearing paths.
Differential protection is normally evaluated around its defined transformer zone and measurement arrangement. Overcurrent protection is evaluated against external faults, backup responsibilities, device coordination and transformer through-fault exposure time.
IEEE C57.109 links the application of overcurrent protective devices to limiting liquid-immersed transformer exposure time during short-circuit current. That is a coordination boundary, not permission to use a generic curve or an overload statement.
The same relay family can be used on projects with different source impedance, CT performance, grounding, vector group, breaker arrangement and communication architecture. A previous setting file is useful only as controlled project history; it is not a substitute for the approved current study and design review.
If information is missing, record the gap before release for manufacture or commissioning. The responsible protection engineer should decide whether the gap changes the scheme, the test plan or the operating restriction.
Selectivity means the planned device or zone responds for the defined fault while adjacent protection retains its assigned backup role. The protection philosophy should state the intended protection zones, primary and backup responsibilities, breaker-failure treatment, intertrips, blocking conditions and restoration rules.
A trip matrix turns that philosophy into accountable interfaces. It should distinguish trip outputs, alarms, indications, lockout actions, remote status, permissives and test points instead of grouping every available contact under a general “protection” label.
SCADA or substation communication may carry status, alarms, metering, event records and control permissions. Define protocol requirements, point lists, time synchronization, event-report expectations and cybersecurity ownership as project interfaces; communications availability must not silently become a substitute for local protection action.
The relay supplier, transformer supplier, switchgear supplier, panel builder and project protection authority should each have a defined document and test responsibility. A clear responsibility split is often more valuable than adding functions that no party owns end to end.
Commissioning evidence should demonstrate that the installed wiring, measured inputs and intended outputs match the approved documents. It normally includes controlled settings documentation, relay configuration records, CT polarity and circuit checks, I/O verification, trip-circuit tests, interlock checks, event-record review and an agreed defect-resolution process.
For condition devices, retain evidence that each supplied contact was identified, wired to the intended terminal, assigned correctly in the trip matrix and tested as an alarm, trip or indication. Include the approved response for unavailable signals or deliberately unused contacts.
Relay event reporting and oscillography can help confirm behavior during testing and after a fault. The commissioning authority still needs to review the full evidence package, outstanding deviations and operational constraints before deciding whether the equipment may be energized.
Related input work may also include the parallel-operation and fault-duty review and PV booster-station interface data. For site preparation, use the transformer installation guidance alongside the approved project documents.
An RFQ should ask for the transformer and protection interfaces as one controlled package. Send the latest one-line diagram, transformer data sheet, winding and vector-group details, grounding arrangement, CT schedule, proposed operating states, available fault-study cases, protection philosophy, trip-matrix requirements, control voltage, SCADA point list and commissioning documentation requirements.
State the responsibility boundary in the enquiry: identify who owns the protection study, setting approval, panel integration, cable termination, site tests and energization authorization. Suppliers can then identify equipment interfaces, data gaps and exclusions without being asked to infer an unstated system design.
Where the approved project scope calls for an integrated transformer and MV interface, a JUBANG ZGS Combined Transformer can be discussed as equipment-family context. It should not be selected as proof of a relay scheme, CT arrangement, setting, trip matrix or protection outcome.

Use this guide to prepare and review protection-application inputs. Do not use it to set relay values, approve a coordination study, determine a mechanical-device action, authorize switching or claim compliance for a specific transformer installation.
For a project-specific discussion, contact JUBANG with the controlled input package and the named protection-design authority.
Schemes may combine differential, overcurrent, earth-fault, breaker-failure and monitoring functions, but the selected functions depend on transformer construction, system arrangement and the approved protection philosophy. Start with required fault coverage and interfaces rather than a fixed relay list.
Differential protection compares currents associated with the protected transformer zone to identify certain internal-fault conditions. Its design depends on verified CT data, winding connections, transformer ratio and the relay application method.
CT location, ratio, polarity, secondary rating and assigned protection core affect the currents presented to the relay. Incomplete or unverified CT information can invalidate the application review and site test results.
Differential protection is normally considered for a defined transformer zone, while overcurrent functions can provide backup and coordinate with adjacent devices for defined fault cases. The final relationship must be demonstrated in the project protection study.
Earth-fault coverage depends on winding connection, neutral availability, grounding method, CT arrangement and the faults identified by the system study. The protection authority should confirm the required function and coordination boundary for the actual network.
A Buchholz relay is a condition device associated with applicable oil-immersed transformer arrangements and may provide contacts for conditions related to gas accumulation or oil movement. Confirm that the device is supplied and document its intended alarm or trip action in the project logic.
The approved project protection authority sets the coordination approach, verifies the study cases and approves the final settings and trip logic. Equipment suppliers provide verified data, interfaces and test evidence within their documented scope.
Include the one-line diagram, transformer data, vector group, grounding, CT schedule, fault-study cases, operating states, protection philosophy, trip matrix, communication requirements and testing responsibilities. This allows suppliers and integrators to identify interfaces and missing data before equipment decisions are fixed.