From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

Explore Jubang Group’s development history, intelligent manufacturing base, R&D platforms, CNAS-accredited laboratory and global project service capabilities.

Transformer insulation resistance testing is a controlled DC diagnostic measurement of the insulation paths selected in an approved test plan. Its useful result includes the winding and ground connections, test voltage, timing, temperature, safety steps and comparable history—not only the resistance displayed by the instrument. A single IR or polarization-index result can prompt investigation, but it does not supply a universal acceptance decision or authorize energization.

An IR test applies DC voltage to an insulation path and observes the resulting insulation resistance. The IEEE guide for diagnostic field testing of liquid-filled transformers treats diagnostic measurements as evidence that must be interpreted together, and notes that manufacturer criteria may take precedence. That is the right starting point for a transformer test plan: define what question each measurement is intended to answer.
State the transformer construction, winding groups, terminals available, accessories connected, condition of liquid or enclosure, test owner and governing procedure. Identify whether the purpose is receiving inspection, post-installation baseline, maintenance trend, fault investigation or a prerequisite to another approved test. These purposes may require different connections, test conditions and escalation paths.
| Scope item | Why it belongs in the plan | Decision owner |
|---|---|---|
| Transformer identity and construction | Keeps dry-type, liquid-filled and special designs from being treated as one insulation system | OEM and project engineer |
| Winding groups and terminal diagram | Defines the insulation paths actually being assessed | Test lead and OEM |
| Test purpose and governing procedure | Prevents a diagnostic spot test from being represented as acceptance | Owner and commissioning lead |
| Connected auxiliaries and external circuits | Identifies equipment that must be isolated or separately protected | Test lead and site electrical lead |
| Required comparison record | Establishes the factory, baseline or prior field data that can be meaningfully compared | Asset owner |
IR is sensitive to the insulation system and its test condition. Moisture, surface contamination, temperature, connected accessories, leakage paths, cleanliness and the test arrangement can influence a result. The Megger transformer-testing overview also identifies temperature dependence in transformer DC insulation measurements.
That sensitivity makes a low or changed reading a reason to pause, document and investigate—not a diagnosis by itself. A high reading is also not proof that every insulation path, bushing, winding turn or dielectric mechanism is healthy. The test scope determines what was challenged; it does not silently extend to functions that the selected connection did not assess.
| Reading context | What the result can support | What it cannot support alone |
|---|---|---|
| Comparable baseline, same arrangement and documented temperature | A trend review of the selected insulation path | A universal condition ranking |
| Unexpected low or unstable value | A need to check condition, setup and related evidence | A confirmed moisture mechanism or failure location |
| Stable value after a controlled retest | A better basis for comparison | Authorization to energize |
| IR combined with other approved diagnostics | A broader engineering review | Replacement of OEM or project acceptance criteria |
For related site-readiness work, see oil-immersed transformer installation before energization. The installation workflow and this IR article are complementary: one organizes commissioning readiness, while the other preserves the limits of one diagnostic measurement.
The test plan should name each planned insulation path. Common categories include a selected winding group to earth, another winding group to earth, and winding-to-winding insulation. The exact sequence, winding terminals joined together, grounded windings, tank or core connection and guard arrangement must follow the transformer diagram, OEM procedure and approved project method.
Do not assume that a label such as “HV to ground” tells every test lead what to do. Record the terminal identification and whether terminals within a winding group are linked.
Also record the non-tested winding groups that are grounded and whether the tank, core, neutral, surge arrester, cable, control circuit or monitoring device remains connected. The EEP procedure overview illustrates why external circuits and accessories need to be considered before winding measurements.
| Record for each measurement | Why it matters |
|---|---|
| Winding group under test | Identifies the insulation path under DC stress |
| Joined terminals and open links | Makes the connection repeatable |
| Grounded windings, tank and core | Defines the return path and prevents ambiguous comparison |
| Isolated cables, arresters, fans, meters and controls | Avoids measuring a parallel circuit or exposing an accessory |
| Guard lead, if the approved method uses one | Identifies the surface or path excluded from the measurement |
| Test-lead and discharge status | Supports safe handover between measurements |
Before touching a lead, the transformer must be isolated, secured under the site safety system and verified de-energized. Residual charge is a hazard. Megger’s safety guidance emphasizes discharge before testing and a controlled discharge after testing; retain the earth until the authorized procedure permits its removal.
Test voltage and test duration are not decorative fields in a result sheet. They influence the electrical stress applied and the value observed over time. The voltage must be selected for the transformer, insulation system, test objective, connected equipment and governing procedure—not copied from a generic online table.
A spot IR test and a timed measurement are different requests. State whether the plan needs a defined point-in-time reading, a sequence of timed readings, or a PI calculation. Also record the instrument model, selected range, actual applied voltage where available, start and finish times, test interruption, leakage-current indication and any automatic discharge behavior.
| Test-plan input | Why it is needed |
|---|---|
| Approved DC test voltage | Confirms the selected stress matches the equipment and procedure |
| Reading intervals and total duration | Makes a spot result, time-resistance curve or PI calculation unambiguous |
| Instrument and calibration status | Preserves traceability and range limitations |
| Test sequence | Prevents a later measurement from being affected by an unfinished discharge or changed connection |
| Aborted-test rule | Defines when a reading is invalid and must be repeated under safe conditions |
Use the OEM and contract procedure when they specify a voltage or timing method. If those documents conflict, resolve the responsibility before testing. An ad hoc increase in DC test voltage is not a substitute for a documented diagnostic strategy.
Temperature changes the insulation-resistance result. Record the winding or relevant insulation temperature, how it was measured, ambient condition, equipment state and the time since any change in operating condition. A number without its temperature and test arrangement is a weak baseline for a later comparison.
Temperature correction can help organize a trend only when the approved method, insulation system and measurement conditions support it. It does not erase differences in moisture, aging, liquid condition, surface contamination, voltage selection or test geometry. When correction uncertainty is material, a controlled retest at comparable conditions can be more informative than forcing unlike readings onto one reference temperature.

The EEP discussion of transformer diagnostics describes the complexity of transformer insulation systems and the need to interpret diagnostic results in context. Include oil or enclosure condition, humidity exposure, cleaning work, transport or maintenance event, temperature, connection record and test instrument in every baseline package.
| Comparison question | Record needed |
|---|---|
| Was the same insulation path measured? | Winding, ground and guard connection record |
| Were the test conditions alike? | Temperature, ambient, equipment state and moisture exposure |
| Was the same test method used? | Voltage, duration, instrument and timing intervals |
| Did the asset condition change? | Maintenance, transport, liquid handling, cleaning or contamination history |
| Is another diagnostic needed? | OEM recommendation, project procedure and related test results |
Polarization index is a timed ratio: the insulation resistance at ten minutes divided by the reading at one minute. It can describe how the measured resistance changes during a controlled DC application. That definition does not make it a universal transformer health score.
The Megger IR Q&A notes that complex oil-cellulose transformer insulation is not simple to interpret with a general-purpose insulation test.
The EEP diagnostic review similarly warns that PI can be misinterpreted for oil-cellulose systems. It identifies dielectric-response methods as a different route for quantitative moisture assessment.
| Question | IR spot or timed reading | PI |
|---|---|---|
| What is recorded? | Resistance at stated time and conditions | Ratio of stated ten-minute and one-minute readings |
| What is its strongest use? | Comparable baseline or targeted check of the selected path | A test-plan-specific time-response observation |
| What must accompany it? | Connections, voltage, temperature and history | The same context plus insulation-system applicability |
| What must not be assumed? | One result defines all insulation condition | A universal threshold proves dryness or readiness |
Use PI only when the OEM or approved test plan calls for it and defines its interpretation for the transformer construction. Do not transfer a ratio rule from rotating machinery or another insulation system into an oil-filled or dry-type transformer decision without that support.
An unexpected result deserves a structured pause. First confirm safety status, test lead arrangement, discharge completion, terminal identification, isolation of external circuits, instrument setting and the recorded temperature. Then compare against the applicable factory, baseline or prior field record only after confirming that the conditions and test path are comparable.
If the value remains unexpected, bring the result to the OEM and responsible project engineers with the full test record. The next step may be an approved retest, inspection, cleaning review or moisture and liquid-condition investigation.
It may also require bushing assessment, winding-resistance or ratio evidence, dielectric-response work or another method defined by the governing procedure. The IEEE diagnostic guide supports interpreting several test results together rather than treating one measurement as conclusive.
| Situation | Immediate boundary | Escalation input |
|---|---|---|
| Connection or isolation cannot be verified | Do not interpret the reading | Diagram, terminal photos, accessory list and OEM procedure |
| Temperature or equipment condition differs materially from history | Do not make a direct trend claim | Recorded conditions and approved comparison method |
| Value changes after a controlled retest | Do not assign a failure mechanism from IR alone | Full time record, other approved diagnostics and OEM review |
| PI is outside the project expectation | Do not apply a rotating-machine rule | Insulation construction, test-plan basis and relevant diagnostic evidence |
| An energization decision is pending | Do not use IR as authorization | Complete project acceptance package and responsible-engineer decision |
For liquid-condition evidence, transformer oil testing before commissioning addresses a separate test family. For bushing-specific signals, see transformer bushing selection and maintenance signals. Neither article turns an IR result into a universal conclusion.
An RFQ or commissioning test plan should require a result that another qualified team can repeat and interpret. Ask bidders and test providers to identify the procedure, transformer construction covered, terminal diagram, connection states, voltage, timing, temperature record, discharge and earthing method, reporting format and escalation route. Ask them to identify every assumption, exclusion and deviation before work begins.
Use this page to specify and interpret the evidence around transformer insulation resistance testing. It does not select a test voltage, define a universal acceptance limit, publish a temperature correction factor, prove dryness, prescribe a PI limit, choose a dry-out method, replace an OEM procedure or authorize energization. Those decisions remain with the approved project specification, transformer OEM, test contractor and responsible engineering team.
Where the approved equipment and test plan support a dry-type discussion, the JUBANG 35 kV resin-insulated dry-type transformer can be a relevant product-family starting point. It is not a conclusion about the condition, test outcome, rating, certification or suitability of a particular transformer.

Send the transformer nameplate, construction, test scope, connection diagram, OEM procedure, recorded conditions and prior comparable results to Contact JUBANG for a project-specific equipment discussion.
It measures the resistance of a defined insulation path while DC voltage is applied under stated conditions. The result is meaningful only with the recorded connection, voltage, timing, temperature and equipment condition.
The plan should identify each winding-to-ground and, where required, winding-to-winding path, plus every terminal joined, grounded, guarded or isolated. Use the transformer diagram and approved OEM or project procedure to define the exact arrangement.
No. They assess different selected insulation paths and require distinct connection records. Do not infer that one arrangement automatically proves the result of another.
Select it through the approved OEM procedure, project specification, transformer construction and test objective. A generic online voltage table cannot account for connected equipment, insulation system or contractual method.
Only with the temperature record and an approved comparison method. Temperature correction has limits, so a controlled retest at comparable conditions may be more reliable when the conditions differ materially.
No. PI is a timed ratio, and oil-cellulose insulation can be difficult to interpret using a general-purpose ratio. Use it only when the approved transformer test plan defines its role and follow up with the appropriate evidence if results are unexpected.
Possible contributors include moisture, contamination, temperature, surface condition, test connections, external circuits and equipment history. Confirm the setup and conditions first, then investigate with the OEM and approved related diagnostics.
No. IR is one diagnostic input. Energization requires the complete approved commissioning and acceptance decision by the responsible project parties.
Retest or escalate when the connection cannot be verified, conditions are not comparable, a reading is unexpected or unstable, or the result conflicts with history or other diagnostics. Preserve the full record so the next qualified reviewer can compare the same test path.