From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

Explore Jubang Group’s development history, intelligent manufacturing base, R&D platforms, CNAS-accredited laboratory and global project service capabilities.

For a defensible procurement decision, transformer bushing selection begins with the transformer interface and system duty. Then match insulation coordination, continuous current, external pollution exposure, construction evidence, and the maintenance information needed over the asset life.
Project documents—not a universal bushing value—define the acceptable combination. Use the approved transformer drawing, bushing data sheet, system study, applicable standard, OEM instructions, purchaser specification, and responsible engineer’s decision.

The first decision is whether the candidate bushing physically and electrically belongs on the actual transformer position. An insulated bushing carries an energized conductor through a grounded boundary, so the transformer-side drawing, conductor connection, terminal arrangement, flange, gasket interface, clearance envelope, and grounding details are as important as the headline voltage class.
IEC 60137 frames insulated bushings for AC equipment above 1,000 V around defined ratings and tests. Use that standard context with the transformer OEM’s drawings and the purchaser’s specification; a generic photo or a nominal kV label does not establish interchangeability.
| Interface question | Evidence to request | Why it changes selection |
|---|---|---|
| Which transformer position is involved? | HV, LV, neutral, tertiary, or other identified position; drawing revision | Position can change system duty, terminal geometry, and insulation-coordination inputs. |
| How is the conductor connected? | Stud, clamp, cable box, bus, flexible lead, terminal hardware, and torque requirements | The current path and contact system must match the transformer design. |
| What seals and mounting surfaces apply? | Flange drawing, gasket details, oil-side arrangement where applicable, fastener pattern | A nominally similar mounting arrangement can still be incompatible. |
| What must remain clear? | Phase-to-phase and phase-to-ground geometry, enclosure, lead, and lifting constraints | External geometry must work with the complete transformer assembly. |
| What documents control the decision? | Transformer drawing, approved bushing schedule, system study, OEM instructions, and owner specification | These documents establish the actual acceptance basis. |
For installation sequencing that sits outside bushing selection, use the related JUBANG installation and pre-energization guide. It covers the wider transformer release context; this page stays focused on the interface evidence needed before a bushing is selected.
Important: Do not substitute a bushing solely because the nominal voltage appears similar. The transformer-side interface, insulation coordination, terminal loading, and approved drawings must be reviewed together; source context: IEC 60137.
Material names describe different insulation and external-housing choices, not a universal ranking. Condenser-bushing constructions may use oil-impregnated paper (OIP), resin-impregnated paper (RIP), resin-bonded paper, or resin-impregnated synthetics; the actual bushing data sheet must identify the construction offered for the project.
The Megger diagnostic overview groups these insulation families by their condenser-core materials. Translate that terminology into project questions before comparing offers.
The supplier’s confirmed design package should answer those questions.

| Construction or housing question | Selection implication | Evidence to obtain |
|---|---|---|
| OIP, RIP, or another condenser-core family? | Changes the design, liquid-related questions, and maintenance documentation. | Manufacturer data sheet, applicable test record, installation instructions. |
| Porcelain or composite external housing? | Changes mechanical, environmental, contamination, and handling considerations. | Housing material, profile, mechanical-duty information, site exposure review. |
| Is the bushing oil-containing? | Determines whether oil sampling or DGA could be relevant to the asset plan. | Cross-section or OEM confirmation, maintenance plan. |
| Is a test tap provided? | Determines how specified dielectric tests and monitoring arrangements can be made. | Tap type, cap/grounding instructions, test method, safety instructions. |
Avoid converting a construction choice into an unsupported performance promise. A dry condenser core may alter liquid-related concerns, while a composite housing may alter external-surface behaviour, but neither description eliminates the need to verify the offered design against the actual electrical, mechanical, and environmental duty.
Voltage and current must be read as a set of duties rather than as isolated catalogue columns. Specify the highest voltage for the relevant equipment, system arrangement, grounding and switching context, continuous current, expected load profile, terminal connection, and any short-duration or fault-duty data required by the governing design documents.
BIL and SIL belong to the insulation-coordination conversation. In common project usage, BIL concerns lightning-impulse withstand requirements and SIL concerns switching-impulse withstand requirements, but their required values and applicability come from the system study, equipment standard, transformer design, and purchaser specification. They are not interchangeable labels, and a bushing must not be selected from either one alone.
| Specification input | What the buyer should clarify | What not to assume |
|---|---|---|
| Highest voltage for equipment | The applicable equipment rating and the transformer position | That the network’s nominal voltage supplies every bushing rating. |
| Continuous current | Rated current, conductor details, load duty, terminal arrangement, and thermal environment | That a matching kV class proves adequate current or contact duty. |
| BIL / lightning impulse | Required impulse-coordination level and governing document | That one lightning-impulse label covers switching and all temporary stresses. |
| SIL / switching impulse | Whether it applies, the required level, and the system study basis | That every project or voltage class uses the same switching-impulse input. |
| Altitude and environment | Site altitude, ambient conditions, enclosure, and exposure | That a sea-level catalogue condition remains valid at every site. |
Where a higher-voltage transformer package is under review, JUBANG’s 35 kV transformer specification checklist can help organize the wider equipment data. It does not replace the bushing manufacturer’s schedule or the project insulation-coordination review.
Creepage is the surface distance along external insulation between conductive parts at different potentials. It should be specified from the site’s pollution severity and the governing selection method, rather than copied from an unrelated transformer or a supplier’s default configuration.
IEC 60815 is a guide for selecting insulators in polluted conditions. A useful RFQ identifies the local contamination sources, wetting conditions, salt or industrial exposure, cleaning constraints, altitude, mounting orientation, and whether the bushing operates inside an enclosure or directly outdoors. Those facts give the supplier and owner engineer a defensible basis to select the external profile and required creepage.
Surface condition also affects maintenance evidence. Pollution deposits, moisture, tracking marks, chipped porcelain, damaged polymer sheds, or a compromised seal can change the risk picture. A visual observation is not enough to diagnose an internal insulation failure, but it is enough to open a controlled inspection and engineering review.
Tip: Describe the contamination source and washing or access constraints in the RFQ, not only a pollution label. The bushing supplier needs the site conditions that support the selected external-insulation profile; source context: IEC 60815.
Capacitance and dissipation-factor testing can provide useful condition evidence when the correct test arrangement and comparison basis are preserved. In a condenser bushing, Megger’s explanation identifies C1 as the capacitance associated with the main insulation between the central conductor and the test tap, while C2 relates to insulation between the test tap and the grounded flange.
That distinction matters because C1 and C2 do not answer the same question and because the test configuration can affect interpretation. Record the bushing identity, test tap arrangement, equipment state, test voltage and frequency, temperature, correction method where applicable, instrument, connections, previous factory or commissioning value, and the standard/OEM criterion selected for the asset.
The INMR technical discussion notes that dielectric interpretation uses standards, historical data, factory values, and temperature context. For this reason, a changed capacitance or tan-delta result should initiate a validity review before it is treated as a failure mechanism or replacement instruction.
| Signal | Useful question | Controlled next action |
|---|---|---|
| C1 capacitance | Is the result comparable with the bushing’s established baseline and test arrangement? | Confirm identity, tap setup, connections, temperature context, and approved comparison basis. |
| C2 capacitance or loss | Does the result reflect test-tap/flange insulation or an installation-sensitive condition? | Follow the OEM test-tap procedure and investigate measurement conditions before diagnosis. |
| Tan delta / dissipation factor | Is the result repeatable and evaluated with the applicable correction and criterion? | Compare under the documented method; involve the responsible engineer for an unexplained change. |
| Visual condition | Are there leaks, contamination, cracked housing, tracking, or damaged hardware? | Make safe, document the observation, and use the approved abnormal-condition process. |
One tan-delta or capacitance value is therefore a decision input, not a universal replacement command. Baselines, test conditions, trend direction, construction type, and the governing technical documents determine what the owner should do next.
DGA is not a test for every transformer bushing. It can be relevant when the bushing design contains insulating oil and the owner’s maintenance plan calls for oil sampling and dissolved-gas analysis as part of a wider condition review.
The IEEE/IET life-management paper describes a high-voltage bushing strategy that combines routine inspection and testing with power-factor testing, UV scanning, and oil sampling for DGA. That is a useful example of layered evidence, not a universal test interval or a diagnosis rule. A DGA result needs the applicable sampling method, liquid and bushing context, prior history, and engineering interpretation.
Thermal concerns deserve the same discipline. An unexpected infrared pattern, abnormal terminal temperature, loosened hardware, discoloration, corrosion, leakage, audible discharge, or changed electrical-test result may indicate a condition that requires action. It does not, by itself, identify whether the cause is a connection, contact resistance, surface contamination, internal insulation, loading, or the measurement arrangement.
For oil-related records that form part of a broader transformer review, see JUBANG’s transformer oil-testing evidence. Keep the bushing-specific design and the transformer liquid compartment clearly identified; do not assume a transformer-tank result automatically characterizes an oil-containing bushing.
Escalate through the project’s controlled process when an abnormal observation is safety-relevant, repeatable, worsening, inconsistent with the approved baseline, or accompanied by leakage, damage, or suspected terminal distress. Isolate, inspect, retest, repair, or replace only under the responsible owner/OEM/engineer authority and the site safety procedure.
An RFQ should let the supplier evaluate the bushing as part of a transformer and network interface. A request that says only “transformer bushing” forces the supplier to infer the duty, geometry, insulation coordination, pollution exposure, and documentation requirements that the purchaser should control.
JUBANG may be a relevant contact when a buyer is defining a 6–10 kV oil-immersed power transformer scope or a 35 kV oil-immersed transformer package. The transformer-side documentation then needs to coordinate with the bushing schedule.
Send the defined inputs through an OEM/ODM transformer consultation so the equipment scope can be reviewed against the actual project documents.

This article does not establish that JUBANG supplies a particular bushing construction, approves an existing bushing for service, performs field diagnostics, interprets DGA, or authorizes replacement. It is not suitable as a substitute for a transformer drawing review, bushing manufacturer data sheet, insulation-coordination study, OEM instructions, or site engineering decision.
Provide the transformer position, approved interface drawing, conductor and terminal details, highest voltage, continuous current, insulation-coordination inputs, environment, pollution conditions, construction constraints, required documentation, and the governing authority. A nominal voltage alone is not enough.
No. OIP and RIP identify different condenser-core approaches, and the offered design must be evaluated against the transformer interface, safety and environmental requirements, monitoring needs, maintenance plan, and supplier documentation. Ask the supplier to confirm the actual construction rather than inferring it from a product family name.
No. They refer to different impulse-coordination inputs in common project practice. The applicable requirement, level, and test context must come from the system study, equipment standard, transformer design, and purchaser specification.
It changes the external-insulation selection problem. Use the site’s contamination sources, wetting conditions, altitude, installation geometry, access, and applicable pollution-selection guide to define the required creepage and profile; do not reuse a value from another location without review.
C1 is associated with the main insulation between the central conductor and the test tap. C2 is associated with insulation between the test tap and grounded flange. Their test arrangements and interpretation context differ, so record the exact setup and compare against the correct baseline and approved criterion.
No universal rule supports that conclusion. First confirm the bushing identity, test arrangement, connections, temperature context, baseline, and governing method. An unexplained or repeatable change should be reviewed through the owner/OEM/engineer process rather than converted directly into a replacement order.
No. DGA can be relevant to an oil-containing bushing when the maintenance plan calls for oil sampling and dissolved-gas analysis. It is not automatically applicable to every construction, and any result requires the proper liquid, sampling, history, and engineering context.
Escalate unexpected leakage, cracked or damaged housing, tracking marks, abnormal heating, loose or distressed terminal hardware, suspicious noise or discharge indications, or a repeatable change in electrical test evidence. The project safety procedure and responsible technical authority decide the next action.
Include the transformer interface, electrical and thermal duty, insulation-coordination inputs, external environment, construction constraints, test and monitoring requirements, documentation, acceptance authority, and deviation process. The RFQ list in Part 7 is a practical starting structure.