GTRM-12 Solid insulated ring main unit can be used in a variety of environmental conditions, especially for high altitude, day and night temperature changes in the area, because it uses solid epoxy resin as the main insulating medium, will not affect the surrounding environment, compared with SF6 gas insulated ring main unit, it has the use of environmental protection and other features. GTPM-12 Solid insulated ring main unit is widely used. It can be used indoors or outdoors alone, and can also be integrated in high and low voltage pre-installed substation.
Safe fully insulated and fully sealed design
GTRM-12 Solid insulated ring main unit is the primary circuit components sealed in a solid epoxy resin box, with solid insulating material as the main insulating medium. The Incoming and outgoing ends can be connected by cable plug heads, so as to ensure that the ring cabinet is fully insulated and sealed, and not affected by the external environment.
Standard modular design
Ring main unit adopts unit modular design, which is divided into load switch unit, load switch-fuse combination electrical unit, circuit breaker unit, busbar PT unit, cable lifting unit and metering unit, etc. Different unit modules can realize free combination.
Flexible extended design
It can be composed of a variety of standard modules, but also can be designed into a combination of different modules into an expandable unit, through the special busbar connector, to achieve a variety of unit combination, to maximize meet the complex and diverse power supply and distribution design schemes in various regions.
Intelligent design
GTRM-12 Solid insulated ring main unit has intelligent design, can integrate partial discharge sensor, humidity sensor and wireless humidity sensor, and through the coordination with distributed DTU or centralized DTU, so as to realize the remote communication, telemetry, remote control and other distribution network automation functions of primary equipment.

Installation conditions
Altitude: ≤ 4500m;
Environment temperature :-40℃ ~+40℃ , the average temperature within 24 hours does not exceed 35℃ ;
Environment humidity: Daily average ≤ 95%, monthly average ≤ 90%;
Installation environment: No violent vibration and impact, and no fire, explosion risk place;
Seismic capacity :8 degrees, ground horizontal acceleration ≤ 0.4g, ground vertical acceleration ≤ 0.2g.
Note: If the operating environment exceeds the above range, please contact our company.
| Item | Unit | Load
switch unit |
Combined
electrical unit |
Circuit breaker unit | |
| Rated voltage | kV | 12 | 12 | 12 | |
| Rated frequency | Hz | 50 | 50 | 50 | |
| Rated current | A | 630 | 125 | 630 | |
| 1min Power frequency voltage resistant | Phase-to-phase and Phase-to-ground | kV | 42 | 42 | 42 |
| Isolating fracture | kV | 48 | 48 | 48 | |
| Lightning shock
withstand voltage |
Phase-to-phase and Phase-to-ground | kV | 75 | 75 | 75 |
| Isolating fracture | kV | 85 | 85 | 85 | |
| Auxiliary circuit and control circuit power frequency withstand voltage | kV | 2 | 2 | 2 | |
| Rated short-time withstand current | kA | 20 | – | 20 | |
| Rated short-time duration | s | 4 | 4 | ||
| Rated peak withstand current | kA | 50 | – | 50 | |
| Rated short-circuit breaking current | kA | – | 31.5 | 20 | |
| Rated short-circuit closing current | kA | 50 | 50 | 50 | |
| Rated transfer current | A | – | 1700 | – | |
| Rated active load breaking current | A | 630 | – | 630 | |
| Rated closed-loop breaking current | A | 630 | – | 630 | |
| Rated cable charging breaking current | A | 10 | – | 15 | |
| Mechanical life | Load switch/
circuit breaker |
Times |
5000 | 5000 | 10000 |
| Isolation switch/
earthing switch |
3000 | 3000 | 3000 | ||
| Circuit resistance protection | μΩ | ≤ 150 | – | ≤ 150 | |
| Grade | Cabinet body IP4X | ||||
Overall dimension diagram