Low Voltage Electrical

Product

GTM6L Series Earth leakage circuit breaker

Compact structure

Undervoltage protection

Short circuit protection

Overload protection

Selection instructions

Notes:

Residual current action value GTM6L-125/250 default :C: GTM6L-400/630 default:D

A:50、100、200  B:100、200、300  C:200、300、500  D:300、500、1000  E:100、400、800

Extreme non driving time GTM6L-125/250 default :C; GTM6L-400/630 default:D

A:0.06、0.1、0.2  B:0.1、0.3、0.6  C:0.1、0.3、0.5  D:0.1、0.5、1  E:0.2、0.4、0.8  F:0.1、0.4、0.7

Product features

Capable of providing overload, short circuit, and undervoltage protection for equipment;

The indication and adjustment of leakAge parameters can be carried out on the circuit breaker panel;

The rated residual operating current and maximum breaking time can be adjusted according to the actual situation;

The current ranges from 32A to 630A

Model specifications

Model Frame level Rated current(A)
32 40 50 63 80 100 125 140 160 180 200 225 250 315 350 400 500 630
GTM6L-125 125
GTM6L-250 250
GTM6L-400 400
GTM6L-630 630

Technical parameters

Model GTM6L-125 GTM6L-250 GTM6L-400 GTM6L-630
GB/T14048.2
IEC60947-2
Frame level Inm(A) 125 250 400 630
Operating Frequency (Hz) 50 50 50 50
Breaking Type L M H L M H L M H L M H
Poles 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P 3P 3P+N,4P
Rated Current In(A) 32,40,50,63,80,100,125 125,140,160,180,200,225,250 250,315,350,400 400,500,630
Rated Insulation Voltage Ui(V) 1000 1000 1000 1000
Rated Impulse Withstand Voltage Uimp(kV) 8 8 8 8
Rated working voltage Ue(V) AC 400 AC 400 AC 400 AC 400
Arcing distance (mm) ≯50 ≯80 ≯100 ≯100
Rated limit short-circuit breaking capacity Icu(kA) 25 35 50 25 35 50 35 50 70 50 70 100
Rated operating short-circuit breaking capacity Ics(kA) 12.5 25 35 12.5 25 35 25 35 50 35 50 70
Rated short- circuit making capacity Icm(mA) 25%Icu 25%Icu 25%Icu 25%Icu
Rated residual operating current I△n(mA) 30(Only non delay type)
200,300,500(Delayed type)
30(Only non delay type)
200,300,500(Delayed type)
300,500,1000 300,500,1000
Extreme non driving time/delayed type (s) 0.1,0.3,0.5 0.1,0.3,0.5 0.1,0.5,1 0.1,0.5,1
Rated residual non-operating current I△no(mA) I△no=I△n/2 I△no=I△n/2 I△no=I△n/2 I△no=I△n/2
Usage category A A A A
Service Life Mechanical Life(Times) Maintenance free 10000 10000 10000 10000
With maintenance 20000 20000 20000 20000
Electrical life(Times) 4000 4000 2000 2000
Overall dimensions (mm) Width(W) 92 122 92 122 92 122 107 142 107 142 107 142 150 198 150 198 150 198 210 280 210 280 210 280
Length(L) 150 150 150 150 150 150 165 165 165 165 165 165 257 257 257 257 257 257 280 280 280 280 280 280
Height(H) 98 98 98 98 115 115 100 100 100 100 118 118 152 152 152 152 152 152 158 158 158 158 158 158
Installation plate hole size (mm) Width(W) 30 60 30 60 30 60 35 70 35 70 35 70 44 94 44 94 44 94 140 140 140 140 140 140
Length(L) 129 129 129 129 129 129 126 126 126 126 126 126 194 194 194 194 194 194 243 243 243 243 243 243
5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 7 7 7 7 7 7
Optional accessories
Alarm contact 08
Shunt release 10
Auxiliary contact 20
Auxiliary contact+Alarm contact 28
Back-panel wiring R
Plug in back wiring PR
WhatsApp