Switchgear & Ring Main Unit

Product

GT-GIS-12 Gas-Insulated High-Voltage Switchgear

High Strength & High Sealing Performance
Compact Design
Flexible and Versatile Expansion Design
Intelligent Design

Overview

1.1 Scope of Application

The GT-GIS-12 Gas-Insulated High-Voltage Switchgear is independently developed by our company and uses dry air as the insulating medium. It is mainly applied in power generation, power transmission and distribution substations, and power distribution systems for industrial and mining enterprises. It is suitable for control, protection, and monitoring under environmental conditions such as high humidity (or condensation), high altitude, and heavy pollution.

1.2 Installation Conditions

Ambient temperature: upper limit +40℃, lower limit -25℃

Altitude: ≤4000 m; for altitudes above 4000 m or other special operating conditions, consultation is required

Ambient humidity: daily average relative humidity≤95%; monthly average relative humidity≤90% Installation location: the surrounding air shall be free from explosive and corrosive gases; the installation site shall be free from frequent severe vibration or impact

Electromagnetic environment: the amplitude of electromagnetic interference induced in secondary circuits shall not exceed 1.6 kV

Note: For special operating conditions beyond normal service requirements, the user and the manufacturer shall agree through consultation.

1.3 Product Features and Structure

Strong Environmental Adaptability

The primary circuit components are enclosed in a sealed metal gas chamber with a protection rating up to IP67, effectively reducing the impact of environmental factors. It is suitable for areas with severe pollution and high humidity.

Modular Design

The product features a compact size and a tight structure, enabling convenient operation and maintenance. Its volume is only 3/5 of that of conventional air-insulated switchgear, reducing floor space requirements while providing excellent insulation performance and passing insulation tests under high-voltage conditions.

Integrated Design

The circuit breaker, disconnector, and earthing switch are integrated into a single unit, resulting in a more compact and simplified structure.

Intelligent Control Technology

Remote operation and control can be realized, meeting the requirements of unattended operation.

Product Model and Designation

Main Technical Parameters

Main Technical Parameters of GT-GIS-12 Gas-Insulated High-Voltage Switchgear

Model Unit Value
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Current A 630~3150
1-Minute Power- Frequency Withstand Voltage Phase and earth kV 42
Across open contacts of switch and disconnector kV 48
Rated Lightning Impulse Withstand Voltage Phase and earth kV 75
Across open contacts of switch and disconnector kV 85
Auxiliary and Control Circuit Power Frequency Withstand Voltage kV 2
Rated Short-Circuit Breaking Current kA 25/31.5/40
Rated Short-Circuit Making Current(Peak Value) kA 63/80/100
Rated Short-Time Withstand Current kA 25/4,31.5/4,40/4
Rated Peak Withstand Current kA 63/80/100
Annual Gas Leakage Rate %y ≤0.01
Rated Operating Sequence O-0.3s-CO-180s-CO
Insulating Gas Dry Air
Rated Filling Gas Pressure(Gauge Pressure,20℃) MPa 0.03
Alarm Pressure(Gauge Pressure,20℃) MPa 0.01
Minimum Insulation Pressure(Gauge Pressure,20℃) MPa 0
Mechanical Endurance Circuit Breaker Times 10000
Three-Position Switch Times 3000
Degree of Protection Gas Chamber IP67
Enclosure IP4X
Rated Voltage of Auxiliary Circuits V AC/DC220
Overall Dimensions(W×D×H, excluding cabinet door) mm 600×1150×2400(630A~1250A)
800~1000×1700×2400(1600A~3150A)

Note: Cabinet dimensions are subject to agreement.

Overall Dimensions Drawing

WhatsApp
+86 13968737027
Phone
+86 189 6895 3236
Email
jubangexport@mccb.cn