From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

GT-HRM-12 environmental protection gas insulated ring main unit is a 12kV ring main unit standardized customized product independently developed by Jubang Group Co., Ltd.
High strength, high sealing
The core parts of the switching equipment are covered with 2.5mm thick high-quality stainless steel by laser welding, which ensures the airbox sealing reliability, high mechanical strength, good corrosion resistance, and the protection level of the inflatable enclosure reaches IP67; The air box is equipped with explosion-proof diaphragm, which can effectively prevent the damage to people and equipment when the air pressure is too high. All conductive parts are enclosed in the air box, which not only avoids the influence of external environmental factors, but also improves the operation reliability, making it maintenance-free and conforming to the features of miniaturization.
Environmental protection and pollution-free
The insulating medium is zero-level dry air or 99.99% pure N2 in accordance with GB/T 8979-2008. The leakAge of gas will not cause any impact on the external environment, without any recycling treatment.
Perfect mechanical interlocking
With perfect five-guard mechanical interlocking function, all the interlocking functions have been configured in the internal, please operate according to the order of operation instructions, very easy to use.
Flexible and changeable extended design
Modular design, can be a variety of modules through the special busbar connector, diversified unit combination, the maximum to meet the complex and diverse distribution design scheme in China.
Visible fracture
① The earth inspection window adopts the optical imaging principle to maximize the viewing Angle inside the switch.
② The light source is set inside the air box, and the inspection window is used to make the field of vision clear.
③ The lighting source uses LED lamp design, which guarantees the design life of the lamp reliably.
Installation conditions
Altitude: ≤ 2000m;
Environment temperature :-40℃ ~+40℃ , the average temperature within 24 hours does not exceed 35℃ ;
Environment humidity: The average 24-hour relative humidity does not exceed 95%. The average monthly relative humidity does not exceed 90%;
Installation environment: the surrounding air is free from explosive and corrosive gases and fire, and the installation site is free from violent vibration impact;
Seismic capacity :8 degrees, ground horizontal acceleration ≤ 0.4g, ground vertical acceleration ≤ 0.2g.
Note: If the operating environment exceeds the above range, please contact our company.
| Item | Unit | Circuit breaker | Load switch | |
| Rated voltage | kV | 12 | 12 | |
| Rated current | A | 630 | 630 | |
| Rated frequency | Hz | 50 | 50 | |
| Rated
insulation level |
1 min Power frequency withstand voltage (Phase-to-phase and Phase-to-ground) | kV | 42 | 42 |
| 1 min Power frequency withstand voltage (Isolating fracture) | kV | 48 | 48 | |
| Power frequency withstand voltage (Control and auxiliary circuits) | kV | 2 | 2 | |
| Lightning shock withstand voltage
(Phase-to-phase and Phase-to-ground) |
kV | 75 | 75 | |
| Lightning shock withstand voltage (Isolating fracture) | kV | 85 | 85 | |
| Rated short-circuit breaking current | kA | 20 | 20 | |
| Rated short-circuit closing current | kA | 50 | 50 | |
| Rated short-time withstand current | kA | 20 | 20 | |
| Rated short circuit duration | s | 4 | 4 | |
| Rated peak withstand current | kA | 50 | 50 | |
| Take-over current/ Transfer current | A | – | – | |
| Rated operation sequence | – |
0-0.3s-CO-180s-CO |
||
| Rated inflation pressure (gauge pressure at 20℃ ) | MPa | 0.02 | ||
| Annual gas leakAge rate | – | ≤ 0.01% | ||
| Mechanical life | Times | 10000 | 10000 | |
| Main circuit resistance | μΩ | ≤ 180 | ≤ 180 | |
| Unit | A(mm) |
| Unit 1 | 420 |
| Unit 2 | 840 |
| Unit 3 | 1260 |