From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

Explore Jubang Group’s development history, intelligent manufacturing base, R&D platforms, CNAS-accredited laboratory and global project service capabilities.

Dry-type transformer ventilation should be designed from the approved loss schedule and operating duty, then checked against the room, enclosure and site conditions. Transformer kVA is not the room heat load. The heat-rejection basis must account for no-load loss and load loss at the agreed duty, while the room design must preserve a complete route for cooling air and safe access for people.

The room has to reject the heat created by the transformer at its specified operating point. Siemens’ cast-resin planning guide and the SGB-SMIT planning guide both describe the design basis as transformer losses, including core-related no-load loss and winding-related load loss. Ask the OEM for those values at the proposed voltage, frequency, tap, cooling mode and duty rather than estimating heat from nameplate kVA.
No-load loss remains present whenever the transformer is energized. Load loss changes with current, so the engineering package should identify the maximum continuous duty, cyclic duty, overload allowance if any, harmonic content and whether fan-assisted operation is part of the specified duty. A room designed only around a nominal capacity can therefore miss the actual heat condition that the ventilation system must handle.
| Input to freeze | Why the room designer needs it | Who should provide it |
|---|---|---|
| No-load and load loss schedule | Establishes the heat-rejection basis at the agreed condition | Transformer OEM |
| Load profile and maximum duty | Identifies the operating point used for the heat balance | EPC electrical lead or owner |
| Cooling mode and fan-assisted duty | Defines whether auxiliary cooling is assumed | Transformer OEM and controls designer |
| Harmonic and waveform information | Allows the OEM to confirm whether the stated loss basis remains applicable | Electrical designer and inverter/drive supplier |
| Number of energized units and diversity | Prevents an incomplete room heat balance | EPC electrical lead |
Use the approved loss schedule with the actual room and air-path data. IEC 60076-11 includes a naturally ventilated-room annex and distinguishes non-enclosed, enclosed and totally enclosed dry-type transformer arrangements. That distinction matters because an enclosure changes how air reaches the transformer and leaves the equipment boundary.
Natural ventilation may be practical in one room and inadequate in another with the same transformer. The answer depends on the approved loss case, inlet-air condition, available height, opening locations, effective free area, duct geometry, external wind and pressure effects, recirculation risk, acoustic treatment and the resistance introduced by screens, louvers or filters. Where the project calculation selects mechanical ventilation, specify the fan duty against the complete system pressure, not a free-air catalogue figure.
Do not use a published airflow ratio or opening size as a universal room design. Supplier guides provide examples and calculation methods, but the OEM’s cooling arrangement, the enclosure drawing and the project’s mechanical design remain controlling.
| Ventilation input | Drawing or calculation evidence | Review question |
|---|---|---|
| Inlet-air temperature and source | Mechanical basis of design and seasonal data | Is the temperature measured at the transformer air intake? |
| Intake and exhaust locations | Room plan, sections and elevations | Does air travel through the transformer rather than bypass it? |
| Louver, screen and filter free area | Manufacturer data and pressure-drop schedule | Has the effective open area, not just the architectural opening, been used? |
| Duct route and discharge location | HVAC layout and external elevation | Can hot exhaust recirculate into the intake or affect nearby equipment? |
| Fan duty, redundancy and power source | Fan curve, control narrative and one-line diagram | Is the duty verified at the system resistance and required operating state? |
Cooling air needs an unobstructed route into the transformer, across the active cooling surfaces and out of the room. The ABB dry-type transformer design guide also links room layout to free air movement, inspection and maintenance. Put that physical path on the coordinated plan and sections before procurement.

Request the outline drawing, cooling-air direction, terminal arrangement, enclosure details, lifting points, cable-entry space and required service envelope from the selected OEM. Show walls, doors, louvers, ducts, cable trenches, switchgear, structural beams and any other equipment that can obstruct airflow or access. A generic spacing value does not replace the manufacturer’s documented requirement or the project’s electrical, fire and access rules.
Plan inspection, cleaning, sensor checks, terminal work and safe replacement of serviceable items without turning a maintenance task into an HVAC demolition scope. Include the control-panel door swing, fan access, filter service route, lifting/handling path and the isolation arrangement used before maintenance. If the room is part of a prefabricated substation, verify the same points against the integrated enclosure boundary rather than assuming a standalone-room layout applies.
At a dry-type transformer, ambient air acts as part of the cooling medium. IEC 60076-11 identifies restricted ventilation, altitude, humidity, damaging fumes and vapours, dripping water, salt spray, conductive pollution, excessive dust and other conditions as service conditions that must be considered beyond normal assumptions. The EPC team should record the actual site exposure and require the transformer OEM to state any design, enclosure, insulation or maintenance implications.
| Site condition | Information to place in the input package | Coordination consequence |
|---|---|---|
| Ambient temperature | Project design temperatures and measurement location | Confirms the cooling-air basis |
| Altitude | Site elevation | Allows OEM review of cooling and insulation assumptions |
| Dust, fibres and conductive contamination | Source, severity, expected deposition and cleaning constraints | Determines whether filtration, enclosure and maintenance strategy need review |
| Humidity, condensation, water or salt exposure | Location, seasonal behavior and ingress paths | Coordinates enclosure, drainage and corrosion protection |
| Corrosive gases or vapours | Process source and concentration data where available | Requires OEM and environmental review |
| Seismic, vibration and sound constraints | Project criteria and adjacent occupancy | Coordinates structural, acoustic and equipment requirements |
Clean air is beneficial, but filtration is not a free add-on: it can change pressure drop, maintenance workload and the air path. Likewise, an enclosure can help address an exposure while creating a ventilation constraint. Treat these as a single equipment-and-room decision.
Fire strategy reaches the transformer room through ventilation penetrations, room boundaries, cable routes, detection, shutdown signals and emergency access. The Siemens planning guidance specifically flags fire-damper coordination where an air duct crosses a fire wall. That is an interface to be designed with the fire engineer and the responsible local authority, not a claim that one damper type or fire arrangement applies everywhere.
Put the following decisions on the multidisciplinary review list:
The transformer supplier should receive the approved room/fire interface information that affects equipment selection or controls. The supplier should not be asked to certify a whole-room solution from a one-line diagram alone.
Temperature monitoring is most useful when the measurement, fan control, alarms, trip philosophy and operator response are designed as one interface. The Eaton TC-100 data sheet illustrates functions that may be specified on a dry-type controller, including winding-temperature inputs, fan relays, alarm/trip outputs, sensor diagnostics and communications. Those are examples of available functions, not assumed equipment scope.
Define who supplies embedded sensors, the controller, fan starters, control power, interfaces to protection and SCADA, alarm annunciation, event records and functional test points. The protection engineer must approve the alarm and trip philosophy; the transformer OEM must confirm compatible sensors and limits; the controls team must own communications and cause-and-effect documentation.
Maintenance access belongs in that same package. Record how filters, fans, sensors, terminal covers and the controller can be inspected or replaced, who isolates the equipment, and what evidence demonstrates that fans and alarms still operate after commissioning. A useful room is one that can be maintained without compromising the intended cooling path.
An effective RFQ lets each bidder state what is included, what data were used and where a deviation needs resolution. It should not ask a supplier to infer room conditions or guarantee compliance with an unnamed code route. Use one controlled revision for the electrical, mechanical and fire-interface inputs.
For readers who need construction terminology before reviewing the room inputs, this SCB14 dry-type transformer overview provides product-family background. Keep that background separate from the project-specific ventilation and room-design decision.
For a project whose approved inputs support a resin-insulated dry-type arrangement, the JUBANG 35 kV resin-insulated dry-type transformer can be a relevant product-family discussion point. It is not a pre-approved answer for every room. Ask for a configuration review against the approved loss schedule, drawings, environment and project requirements.

Send JUBANG the approved loss schedule, one-line diagram, room plan, site conditions and required document list through the contact page for a project-specific review.
Ventilation removes heat, so the design basis is the OEM loss schedule at the agreed operating condition. No-load loss and load loss must be considered with the duty, cooling mode and number of energized units.
No. Airflow depends on the approved heat basis, room geometry, intake-air condition, enclosure, pressure losses and OEM cooling arrangement. Use the project calculation and manufacturer documentation.
No. An enclosure changes the cooling-air route, while the room still has to supply acceptable intake air and reject the exhaust heat. Review the enclosure and room as one system.
Include design temperatures, altitude, humidity, condensation risk, dust, pollution, salt, water exposure, corrosive gases, seismic conditions and acoustic constraints. The OEM can then state the required equipment response or exclusions.
Yes. Room boundaries, duct penetrations, detection, fan shutdown or operation, cable seals and emergency access are cross-discipline interfaces. The fire engineer and local authority determine the applicable strategy.
Define sensor supply and type, controller scope, fan control, alarm and trip interfaces, control power, communications, test points and responsibility for settings. Do not assume a controller function is included without an agreed specification.
It is not automatic when the room conditions, environmental exposure, heat-rejection path, fire strategy, access constraints or project requirements have not been resolved. Compare suitable technologies only after the approved input package is complete.