Power Transformer

Product

On-load Tap-Changing Dry-Type Distribution Transformer

Optimized Magnetic Circuit
Energy Saving & Reduced Loss
Low Noise
Strong Overload Capability
Compact Structure

Overview

1.2 Applicable Standards

GB/T10228 GB/T1094.11 GB/T4208 GB20052 GB/T1094.1 GB/T1094.12 JB/T10088

Technical Data

Technical Data of SCZ(B)10 Series 6kV/10kV On-Load Tap-Changing Dry-Type Distribution Transformers

Rated Capacity(KVA) Voltage Combination & Tapping Range Vector Group No-Load Loss(kW) Load Loss(KW) at Different
Insulation Thermal Classes
No-Load Current(%) Short-Circuit Impedance(%)
HV HV Tapping Range(%) LV Class B (130℃/100℃) Class F (155℃/120℃) Class H (180℃/145℃)
315 6
6.3
6.6
10
10.5
11
±4×2.5 0.4 Dyn11
Yyn0
0.99  3.40  3.61  3.86 1.1 4
400 1.12  4.02  4.27  4.57 1.1
500 1.29  4.92  5.22  5.58 1.1
630 1.49  5.82  6.17  6.60 1.0
630 1  6  6  7  1 6
800 1.71  7.07  7.50  8.02 1.0
1000 2  8  9  9  1
1250 2  10  10  11  1
1600 2.72  11.7  12.4  13.3 0.85
2000 3.42  14.3  15.2  16.2 0.7
2500 3.96  17.1  18.1  19.4 0.7

 

Technical Data of SCZ(B)11 Series 6kV/10kV On-Load Tap-Changing Dry-Type Distribution Transformers

Rated Capacity(KVA) Voltage Combination & Tapping Range Vector Group No-Load Loss(kW) Load Loss(KW) at Different
Insulation Thermal Classes
No-Load Current(%) Short-Circuit Impedance(%)
HV HV Tapping Range(%) LV Class B (130℃/100℃) Class F (155℃/120℃) Class H (180℃/145℃)
315 6
6.3
6.6
10
10.5
11
±4×2.5 0.4 Dyn11
Yyn0
0.89  3.40  3.61  3.86 1.1 4
400 1.00  4.02  4.27  4.57 1.1
500 1.16  4.92  5.22  5.58 1.1
630 1.34  5.82  6.17  6.60 1.0
630 1.29 6.00 6.36 6.80 1.0 6
800 1.54  7.07  7.50  8.02 1.0
1000 1.78 8.28 8.78 9.39 0.85
1250 2.10 9.86 10.4 11.1 0.85
1600 2.45  11.7  12.4  13.3 0.85
2000 3.08  14.3  15.2  16.2 0.7
2500 3.56  17.1  18.1  19.4 0.7

 

Technical Data of SCZ(B)12 Series 6kV/10kV On-Load Tap-Changing Dry-Type Distribution Transformers

Rated Capacity(KVA) Voltage Combination & Tapping Range Vector Group No-Load Loss(kW) Load Loss(KW) at Different
Insulation Thermal Classes
No-Load Current(%) Short-Circuit Impedance(%)
HV HV Tapping Range(%) LV Class B (130℃/100℃) Class F (155℃/120℃) Class H (180℃/145℃)
315 6
6.3
6.6
10
10.5
11
±4×2.5 0.4 Dyn11
Yyn0
0.79  3.40  3.61  3.86 0.8 4
400 0.89  4.02  4.27  4.57 0.8
500 1.03  4.92  5.22  5.58 0.7
630 1.19  5.82  6.17  6.60 0.7
630 1.15 6.00 6.36 6.80 0.7 6
800 1.37  7.07  7.50  8.02 0.7
1000 1.58 8.28 8.78 9.39 0.7
1250 1.87 9.86 10.40 11.10 0.7
1600 2.17  11.70 12.40 13.30 0.7
2000 2.73  14.30 15.20 16.20 0.6
2500 3.17  17.10 18.10 19.40 0.6

Notes:

The load loss values listed in the table correspond to different insulation systems at the reference temperatures specified in parentheses in GB/T1094.11. Load loss values for other insulation systems not included in the table shall be converted according to their respective reference temperatures, using the data for the 155℃ (Class F) insulation system as the reference.