Power Transformer

Product

Three-Dimensional Wound Core Transformer

Optimized Magnetic Circuit
Energy Saving & Reduced Loss
Low Noise
Strong Overload Capability
Compact Structure

Overview

1.1 Product Features

The three-dimensional wound core transformer is a high-efficiency and energy-saving power transformer. It innovatively replaces the traditional laminated core structure and three-phase layout used in conventional transformers, resulting in optimized performance. With a fully symmetrical three-phase magnetic circuit, the transformer achieves significant energy-saving performance, greatly reduced noise, improved heat dissipation capability, stronger overload capacity, and a compact structure.

1.2 Magnetic Circuit Optimization

① The three-dimensional wound core has no joints, ensuring uniform magnetic distribution throughout the magnetic circuit without obvious high-flux regions or sudden changes in magnetic flux density caused by joints.

② The magnetic flux direction is fully consistent with the grain orientation of the silicon steel sheet.

③ The three-phase magnetic path lengths are completely equal, achieving the shortest possible magnetic circuit.

④ The three-phase magnetic circuits are perfectly symmetrical, resulting in fully balanced three-phase no-load currents.

1.3 Low Loss and Significant Energy-Saving Effect

① The magnetic flux direction of the three-dimensional wound core is completely consistent with the rolling direction of the silicon steel sheet. In addition, the core layers are continuously wound without overlapping joints, resulting in uniform magnetic flux distribution without obvious high-flux regions or sudden flux density changes. Under the same material conditions, compared with traditional laminated cores, the core process coefficient is reduced from 1.3-1.5 to about 1.05, which alone can reduce core loss by 10-20%.

② Due to the special three-dimensional structure, the core weight is reduced by about 25% compared with traditional laminated cores, and the corner weight accounts for about 6% of the total core weight.

③ After shearing, the silicon steel sheets undergo magnetic property annealing treatment. The three-dimensional wound core is subjected to high-temperature (about 800℃) vacuum annealing, which eliminates internal stress and refines the magnetic domains of the silicon steel sheet, significantly improving its magnetic properties.

④ Test results show that the no-load loss of the three-dimensional wound core transformer can be reduced by 25-35% compared with national standards, and the no-load current can be reduced by up to 92%.

1.4 Low Noise

The three-dimensional wound core is manufactured by continuously winding silicon steel strips on a dedicated core winding machine, forming a compact structure without joints. This eliminates noise caused by discontinuous magnetic circuits commonly found in laminated cores.

At the same time, the three-phase magnetic circuit is symmetrical and the operating magnetic density is properly designed, which significantly reduces transformer noise.

According to tests, the noise level of the transformer can be as low as 47 dB, which is 19 dB lower than the standard limit of 66 dB, approaching environmental silence standards and making it particularly suitable for indoor installations and residential areas.

1.5 Strong Overload Capacity

① The transformer itself generates very little heat. The no-load loss and no-load current of the wound core transformer are extremely low, resulting in minimal heat generation during operation.

② The three-phase windings are arranged in a “品”-shaped configuration. A natural ventilation channel-known as the chimney effect-is formed in the center of the windings. As the iron core heats up to approximately 30-40℃, air is heated and rises naturally. Cooler air is drawn in from the lower central channel, and heat is dissipated outward from the iron core, enabling natural circulation and rapid heat removal from the transformer.

1.6 Compact Structure and Small Footprint

The special three-dimensional wound core structure results in a compact and well-organized layout.

The plan area of the transformer body is reduced by about 10-15% compared with conventional

transformers.

The overall height is reduced by approximately 10-20%

When installed in a box-type substation, the enclosure volume can be reduced by about one quarter.

Main Technical Parameters

Main Technical Parameters of 6kV/10kV S13-M.RL Series Grade 3 Energy-Efficient Three-Dimensional Wound Core Off-Circuit Tap-Changing Transformers

Rated Capacity(kVA) Voltage Combination & Tapping Range Vector Group No-load Loss(W) Load Loss(W) Short-circuit Impedance(%) No-load Current(%)
HV(kV) HV Tapping Range(%) LV(kV)
30 6
6.3
10
10.5
11
±2×2.5
±5
0.4 Dyn11
Yzn11
Yyn0
80 630/600 4 0.3
50 100 910/870 4 0.24
63 110 1090/1040 4 0.23
80 130 1310/1250 4 0.22
100 150 1580/1500 4 0.21
125 170 1890/1800 4 0.2
160 200 2310/2200 4 0.19
200 240 2730/2600 4 0.18
250 290 3200/3050 4 0.17
315 340 3830/3650 4 0.16
400 410 4520/4300 4 0.16
500 Dyn11
Yyn0
480 5410/5150 4 0.16
630 570 6200 4.5 0.15
800 700 7500 4.5 0.15
1000 830 10300 4.5 0.14
1250 970 12000 4.5 0.13
1600 1170 14500 4.5

 

Main Technical Parameters of 6kV/10kV S20-M.RL Series Grade 2 Energy-Efficient Three-Dimensional Wound Core Off-Circuit Tap-Changing Transformers

Rated Capacity(kVA) Voltage Combination & Tapping Range Vector Group No-load Loss(kW) Load Loss(kW) Short-circuit Impedance(%) No-load Current(%)
HV(kV) HV Tapping Range(%) LV(kV)
30 6
6.3
10
10.5
11
±2×2.5
±5
0.4 Dyn11
Yzn11
Yyn0
70 505/480 4 0.3
50 90 730/695 4 0.24
63 100 870/830 4 0.23
80 115 1050/1000 4 0.22
100 135 1265/1200 4 0.21
125 150 1510/1440 4 0.2
160 180 1850/1760 4 0.19
200 215 2185/2080 4 0.18
250 260 2560/2440 4 0.17
315 305 3065/2920 4 0.16
400 370 3615/3440 4 0.16
500 Dyn11
Yyn0
430 4330/4120 4 0.16
630 510 4960 4.5 0.15
800 630 6000 4.5 0.15
1000 745 8240 4.5 0.14
1250 870 9600 4.5 0.13
1600 1050 11600 4.5 0.12

 

Main Technical Parameters of 6kV/10kV S22-M.RL Series Grade 1 Energy-Efficient Three-Dimensional Wound Core Off-Circuit Tap-Changing Transformers

Rated Capacity(kVA) Voltage Combination & Tapping Range Vector Group No-load Loss(W) Load Loss(W) Short-circuit Impedance(%) No-load Current(%)
HV(kV) HV Tapping Range(%) LV(kV)
30 6
6.3
10
10.5
11
±2×2.5
±5
0.4 Dyn11
Yzn11
Yyn0
65 455/430 4 0.3
50 80 655/625 4 0.24
63 90 785/745 4 0.23
80 105 945/900 4 0.22
100 120 1140/1080 4 0.21
125 135 1360/1295 4 0.2
160 160 1665/1585 4 0.19
200 190 1970/1870 4 0.18
250 230 2300/2195 4 0.17
315 270 2760/2630 4 0.16
400 330 3250/3095 4 0.16
500 385 3900/3710 4 0.16
630 460 4460 4.5 0.15
800 560 5400 4.5 0.15
1000 665 7415 4.5 0.14
1250 780 8640 4.5 0.13
1600 940 10440 4.5 0.12

Notes:

① For transformers ≤500 kVA, load loss above the diagonal line applies to Dyn11/Yzn11, and load loss below the diagonal line applies to Yyn0.

② LV = 0.69 kV is available upon request.

③ Low-loss design is available upon request.