Medium Voltage Switches & Pole-Mounted Circuit Breakers

Product

ZW32-15.5 Outdoor VCB

Fast Response
Accurate Fault Sectionalizing
Integrated Casting Design
Simultaneous Acquisition of Incoming & Outgoing Signals

Product Features

Permanent Magnet Actuation Mechanism

Faster response and higher fault discrimination accuracy; fault clearing time <10ms

Solid Insulation Technology

The vacuum interrupter, flexible connections, and voltage/current sensors are fully encapsulated and integrally cast inside epoxy insulation

Real-time Acquisition of Line-side Signals

Simultaneous monitoring of incoming and outgoing line voltage and current signals, with intelligent power supply for line-side terminals

Compliance with International Standards

Fully compliant with IEC 62271-111

Main Technical Parameters Table

Main Technical Parameters of ZW32-15.5 Outdoor HV AC Permanent Magnet VCB

Model Unit ZW32-15.5
Rated Voltage kV 15
Rated Frequency Hz 50/60
Rated Current A 800
Rated Short-circuit Breaking Current kA 20
Rated Peak Withstand Current 50
Rated Short-time Withstand Current(3s) 20
Rated Short-circuit Making Current(Peak) 50
Rated Operating Sequence O-0.5s-CO-2s-CO-2s-CO-2s-CO
Mechanical Endurance Times 10000
Rated Number of Short-circuit Breaking Operations Times 30
Power-frequency Withstand Voltage(1min) Phase-to-phase,Phase-to-earth/Across Open Contacts kV 50
Lightning Impulse Withstand Voltage
(Phase-to-phase, Phase-to-earth/Across Open Contacts)
110
Overall Partial Discharge of the Complete Unit Test Voltage kV 9.6
Partial Discharge(PD) PC ≤20
Rated Operating Voltage
(Customizable upon Request)
V DC220
Operating Mode/Operating Method