Low Voltage Electrical

Product

GTW1 Air Circuit Breaker

Intelligent
High breaking
Monitoring function
Fault memory function

Selection instructions

Product Features

•Intelligent and high breaking;
• Equipped with 3 and 4 poles, drawer type and fixed type, and can be installed with reverse wire;
• Equipped with multiple intelligent controllers, providing three-stage/four stage protection functions, monitoring functions, fault memory functions, and communication interfaces, it can achieve telemetry, remote adjustment, remote control, and remote communication;
• Complies with GB/T14048.2 and IEC60947-2 standards;
• Complete protection characteristics, convenient setting, high accuracy, with instantaneous, short delay, long delay grounding and other protection characteristics;
• The current ranges from 200A~6300A and the short-circuit breaking capacity is 50kA~120kA.

Technical parameters

Model GTW1-1600 GTW1-2500 GTW1-3200 GTW1-4000 GTW1-6300
GB/T14048.2
IEC60947-2
Frame level current Inm(A) 1600 2500 3200 4000 6300
Electrical performance
Poles 3P 4P 3P 4P 3P 4P 3P 4P 3P 4P 3P
Operating frequency (Hz) 50 50 50 50 50
Rated working voltage Ue(V) AC 400/690 AC 400/690 AC 400/690 AC 400/690
Rated current +40℃ In(A) 200,400,630,800,1000,1250,1600 630,800,1000,1250,1600,2000,2500 2000,2500,3200 3200,3600,4000 4000,5000 6300
Rated insulation voltage Ui(V) 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp(kV) 12 12 12 8 8
N-pole rated current In(A) 100% 100% 100% 100% 100%
Breaking type M H M H
Rated limit short-circuit breaking capacity Icu(kA) 400V 65 65 85 85 100 100 120
690V 50 50 55 60 65 65 80
Rated operating short-circuit breaking capacity Ics(kA) 400V 55 65 55 70 65 65 80
690V 42 50 40 55 60 50 70
Rated short-time withstand current (kA/1s) 400V 50 65 55 70 65 65 85
690V 42 50 40 55 65 50 65
Operating time (ms) Opening 23~32 23~32 23~32 23~32 23~32
Closing <70 <70 <70 <70 <70
Arc distance (mm) 0 50mm 50mm 0 0
Service life Mechanical life(times) Maintenance-free 15000 10000 5000 5000 3000
With maintenance 30000 20000 10000 10000 6000
Electrical life(times) 400V 6000 6500 3000 1500 500
690V 3000 3000 1500 750 300
Isolation function
Protection
Intelligent Controller
N-pole Protection capability(only 4P and 3P+N)
Connection and Installation
Usage category B B B B B
Installation category Circuit breaker(including primary coil)
Auxiliary circuit(excluding primary coil)
Pollution level 3 3 3 3 3
Connection method Horizontal/Vertical Horizontal/Vertical Horizontal/Vertical Horizontal Horizontal
Incoming method Up/Down Up/Down Up/Down Up/Down Up/Down
Installation method Fixed type(3/4) Drawer type(3/4) Fixed type(3/4) Drawer type(3/4) Fixed type(3/4) Drawer type(3/4) Drawer type(3/4) Drawer type(3/4) Drawer type(3)
Overal dimensions(mm) Width(W) 265/335 305/375 370/465 410/505 422/537 470/585 585/820 845/960 960
Depth(D) 230 340 340(short)
370(long)
430(short)
460(long)
340(short)
380(long)
430(short)
490(long)
490 490 490
Height(H) 310 345 402 432 402 432 432 432 432

■Standard configuration  □Optional  – None

Ordering specifications

Customer Name : Order quantity : Date :
Model specifications GTW1-1600 □M□H GTW1-2500 □M□H □ GTW1-3200 □ GTW1-4000 □ GTW1-6300
Poles □3:3P □4:4P □3:3P □4:4P □3:3P □4:4P □3:3P □4:4P □3:3P □4:4P
Rated current (A) □200
□400
□630
□800
□1000
□1250
□1600
□200
□400
□630
□800
□1000
□1250
□1600
□630
□800
□1000
□1250
□1600
□2000
□2500
□630
□800
□1000
□1250
□1600
□2000
□2500
□2000
□2500
□3200
□2000
□2500
□3200
□3200
□3600
□4000
□3200
□3600
□4000
□4000
□5000
□6300
□4000
□5000
Installation method □Fixed type                              □Drawer type
Rated voltage (V) □AC400V                                    □AC690V
Controller Digital tube
display
□M type
(■Basic default
configuration)
Protection feature 1 (4 stage protection): Overload long delay protection Ir; Short circuit short time delay protection Is; Short circuit instantaneous protection li; Grounding protection lg; Protection feature 2: Load monitoring (2 methods), distribution protection(optional), prealarm (2 methods), N-phase protection, MCR on/off and analog trip protection.
Functional features: Thermal memory characteristics, parameter setting function, test operation function, fault tripping alarm, various status indications and numerical display; Ammeter function operation, voltmeter function operation, pre alarnn, self-diagnosis function, full light inspection,and date setting function.
□2H type It includes M-type basic and general functions, Modbus RTU cormmunication functions (Telemetry, remote adjustment, remote control, remote communication), circcuit breaker contact wear function voltage display, frequency display, power display, electricity metering, counting function, three-phase imbalance protection, etc.
Remote control function, lock configuration function, HSISC over limit trip protection function.
LCD screen
display
□3M type Including basic and general functions of M type:
LeakAge alarm, overvoltage protection, undervoltage protection, voltage imbalance protection, underrated protection, over-frequency protection, reversepower protection, phase sequence protection;
Measurement functions: Real time signal measurement (voltage, voltage imbalance rate, current, current imbalance rate, phase sequence, frequency, power, power factor, electrical energy), demand measurement, harmonic measurement, measurement meter setting, clock setting, etc
□3H type Includes basic and general functions of the 3M model.
Communication functions (telemetry, remote adjustment, remote control, remote communication), displacement recording, etc.,with all the functions of the aforementioned controller models.
Controller power supply voltage □AC230V           □AC400V           □DC110V        □DC220V
GTW1-2500 above
undervoltage release
□Normal type □Instantaneous □AC230V         □AC400V
□Self-priming type □Instantaneous □AC230V         □AC400V
□Delayed □AC230V         □AC400V
□0.3S     □0.5S     □1S      □3S     □5SAdjustable
□Special customization delay_____s
GTW1-1600 Undervoltage
release
□AC230V                          □AC400V
□Instantaneous             □Delayed(□0.5s    □2s    □3s Optional non adjustable)
□Special customization delay_____s
Shunt release □AC230V      □DC2220V      □AC400V       □DC110V
Closed electromagnet □AC230V      □DC2220V      □AC400V       □DC110V
Energy storage motor □AC230V      □DC2220V      □AC400V       □DC110V
Auxiliary
contact
GTW1-2500
and above
□4 group transfer (Normal)        □Four open and four close       □6 group transfer        □6 open and 6 close
□Special please note
GTW1-1600 □4 group transfer (Normal)          □2 open and 2 close
Special requirements
standard configuration
□Steel cable interlocking (Default 2 meters) special customization_____meters
□Lever interlocking          □ L-shaped wiring
□1 lock 1 key     □3 locks 1 key    □3 locks 2keys    □5 locks 2keys    □Special project___locks___keys
□External N-phase transformer 【(3P+N)T-mode】   □External zero sequence sensor (E mode)
□External ground current sensor (W mode)
□Automatic power transfer system(Unit:_____set)    See notes①

Notes:

①A set of automatic power transfer system comes standard with two GTW1 universal circuit breakers, one automatic transfer controller one set of control cables, and one set of interlocking mechanism. Among them, the voltage of the universal circuit breaker controller power supply, shunt release, closing electromagnet, and energy storage motor should all be AC230V.

②When the user orders without any requirements, the controller is selected as M-type, and the default setting value at the factory is:

a)Set the long delay Ir to 1.0 In and the action time of 1.5 Ir to 15 seconds

b)Set the short delay Is to the value of 8lr and the timing limit to 0.4s

c) Instantaneous li set at 12In

d) Ground fault lg set at 0.4ln, action time 0.4s