From transformers and switchgear to ring main units, substations, circuit breakers and smart components, Jubang provides integrated product support for power distribution projects.

Discover Jubang’s strengths in technology R&D, quality testing and smart manufacturing, supporting reliable electrical equipment and efficient power distribution solutions for global customers.

From technical consultation and OEM/ODM customization to EPC support, smart O&M, delivery documentation and after-sales service, Jubang supports your project at every stage.

● The main body of the vacuum circuit breaker is a pillar structure.
● Equipped with intelligent controller FTU to form a boundary intelligent type.
● Integrated high-voltage primary and secondary components: vacuum circuit breaker, isolation switch, voltage transformer, current transformer, intelligent controller FTU.
● Universal installation dimensions: The installation dimensions for manual and electric operations are consistent.
| Item | Unit | Value | |
| Rated voltage | kV | 40.5 | |
| Rated frequency | Hz | 50 or 60 | |
| Rated current | A | 630、1250、1600 | |
| Rated short-circuit breaking current | kA | 20、25、31.5 | |
| Rated peak withstand current (peak) | 50、63、90 | ||
| Rated short-time withstand current | 20、25、31.5 | ||
| Rated short-circuit making current (peak) | 50、63、80 | ||
| Mechanical lfe | Times | 10000 | |
| Rated short-cicuit breaking curent breaking times | Times | 30 | |
| 1 min power frequency withstand voltage |
Dry type (Interphase and opposite Isolating fracture) |
kV |
95 |
| Wet type | 80 | ||
| Peak value of lightning impulse withstand voltage (Interphase and opposite/lsolating fracture) | 185 | ||
| Partial discharge | PC | ≤20 | |
| Rated operating sequence |
0-0.1s-CO-3s-CO-6s CO-60s Recovery |
||
| Rated operating voltage | V | AC/DC220 | |
| Weight | kg | About 270 | |